Site survey, design and technical quotes for your cold room, blast freezing and industrial refrigeration projects +90 850 346 17 67
Modular Cold Rooms

Monoblock Refrigeration Unit

Through-wall monoblock refrigeration units with natural refrigerant R290. For cold and freezer rooms, in On-Off and energy-saving variable speed series.

RefrigerantR290 (natural refrigerant), max. 150 g per circuit
SeriesOn-Off and energy-saving variable speed
CapacityCold room 0.7–4.4 kW, freezer room 0.5–2.6 kW (+32 °C ambient)
CompressorEmbraco hermetic
Power supplyOn-Off: 220-230 V / 1 ph / 50 Hz · Variable speed: 200-240 V / 1 ph / 50-60 Hz
InstallationThrough-wall, for 70–120 mm panels
ControlEmbraco electronic controller
DefrostHot gas
CondensateEvaporation tray, no drain needed
LightingIn-room LED

Monoblock refrigeration units combine the condenser and evaporator in a single body and work plug-and-play. The unit sits in an opening in the cold room wall, with the condenser outside and the evaporator inside the room. No copper pipework or refrigerant charging is needed on site, so installation is quick. They use the natural refrigerant R290.

Two series

  • On-Off series: the compressor switches on and off as needed. A simple, economical solution.
  • Variable speed series (energy-saving): the compressor adjusts its speed to the room’s demand, using less electricity and keeping the room temperature more stable.

Components

  • Embraco hermetic compressor
  • Embraco ECQ and Ziehl-Abegg fan motors
  • Inner-grooved copper tube condenser and evaporator
  • Danfoss thermostatic expansion valve
  • Hot gas defrost and condensate evaporation tray
  • In-room LED lighting

Cold room models

Room +5 °C, ambient +32 °C.

CodeSeriesCompressorCapacitySuggested room volumeBody
FM.12.001On-Off0.3 HP720 Wup to 8.4 m³M01
FM.60.001Variable speed—865 Wup to 10.2 m³M01
FM.60.005Variable speed—1,243 Wup to 17.2 m³M01
FM.12.005On-Off0.6 HP1,261 Wup to 17.5 m³M01
FM.12.010On-Off0.75 HP1,734 Wup to 26.0 m³M02
FM.60.010Variable speed—1,795 Wup to 26.9 m³M02
FM.60.015Variable speed—2,111 Wup to 32.6 m³M02
FM.12.015On-Off1 HP2,177 Wup to 34.7 m³M02
FM.60.020Variable speed—2,486 Wup to 39.6 m³M03
FM.12.020On-Off2 × 0.6 HP2,522 Wup to 42.4 m³M03
FM.12.025On-Off2 × 0.75 HP3,469 Wup to 61.1 m³M03
FM.60.025Variable speed—3,590 Wup to 63.2 m³M03
FM.60.030Variable speed—4,222 Wup to 75.1 m³M03
FM.12.030On-Off2 × 1 HP4,353 Wup to 80.1 m³M03

Freezer room models

Room −20 °C, ambient +32 °C.

CodeSeriesCompressorCapacitySuggested room volumeBody
FM.17.001On-Off0.75 HP487 Wup to 2.9 m³M01
FM.65.001Variable speed—525 Wup to 3.1 m³M01
FM.17.005On-Off0.75 HP643 Wup to 4.5 m³M01
FM.17.010On-Off1 HP761 Wup to 6.1 m³M02
FM.65.010Variable speed—764 Wup to 6.2 m³M01
FM.17.015On-Off1 HP1,009 Wup to 8.6 m³M02
FM.65.015Variable speed—1,031 Wup to 8.8 m³M02
FM.17.020On-Off2 × 1 HP1,522 Wup to 17.2 m³M03
FM.65.020Variable speed—1,528 Wup to 17.3 m³M03
FM.17.025On-Off2 × 1 HP2,019 Wup to 27.6 m³M03
FM.65.025Variable speed—2,062 Wup to 28.2 m³M03
FM.17.030On-Off2 × 1.25 HP2,572 Wup to 38.4 m³M03

Capacity and suggested room volume vary with room temperature and ambient conditions; each model’s full values are on its data sheet. Suggested room volume applies to rooms with 100 mm panels and standard use.

Installation dimensions

BodyPanel cut-out widthDistance to drain hole
M01362 mm581.6 mm
M02593.4 mm712.6 mm
M03632 mm712.6 mm

Drain hole Ø48 mm; 50 × 32 mm notches at the top corners of the cut-out. Leave at least 250 mm clearance above and behind the unit.

The units are designed for a 220-240 V / 50 Hz single-phase supply. For 60 Hz or other voltages, please contact us.

The right model for your room

Find the monoblock model that suits your room size, temperature and your city’s climate straight away with Smart Quote.

Calculate with Smart Quote